Network filter suppressing interference FSP-3F-10AIN

Filters are designed to protect radio-electronic devices (RU) and computing equipment (CE) from information leakage through primary power supply circuits with a voltage of 380/220 V 50 Hz, as well as to protect them from high-frequency interference, increase their noise immunity and electromagnetic compatibility. FSP-3F-10A-IN - three-phase (four-wire with isolated neutral) with an operating current of up to 10 A for each phase.

TECHNICAL CHARACTERISTICS

FSP-3F-10A

1. Maximum operating current 40 A

Insertion signal attenuation in the frequency range, not less than

0.15 - 300 MHz 70 dB

300 - 1000 MHz 50 dB

3. Voltage drop on filter wires

at max. operating current, no more than 0.5 V

4. Overall dimensions of the case, mm 240x136x112

Weight, kg, no more than 2.0

Electrical protection class according to GOST 12.2.007.0-75 01

When filters are connected in parallel, their corresponding characteristics are summed up.

Order designation: Network filter FSP-3F-10A-IN OSHM3 544 011 TU.